Installation and operating instructions
Compact wall-mounted units KWL EC 200/300 W R/L
9
GB
2.8
Functional layout
Fig. KWL EC 200/300 W Right
Pos.
Name
Item No.
T1
Outside air sensor
-----
T2
Supply air sensor
-----
T3
Extracted air sensor
-----
T4
Outgoing air sensor
-----
T6
Duct sensor Type KWL-LTK (accessories)
09644
T7
Frost-protection sensor Type KWL-LTK (accessories) for WW-register return
09644
T11-T18
Humidity/temperature sensor: KWL-FTF (accessories)
04273
1
Temp-resistant or non-flammable duct (e.g. spiral duct)
-----
2
Iso-Pipe duct Ø 125
-----
3
Connector with seal for unit connection to ductwork: RVBD 125
09640
4
Electric pre-heater internal: KWL EVH 200/300W
04224
5 Electric auxiliary heater Type HER-R 1.2/125 + KWL EM + KWL LTK
09433
04269
09644
Alternative
Hot water auxiliary heater Type: WHR 125
and hydraulic unit + WHSH 1100 24V (0-10V)
+ KWL EM
+ 2x KWL LTK (T6+T7)
09480
08819
04269
09644
2.9
Initial start-up and adjustment
NOTE
Useful hint for adjustment!
The adjustment by means of pressure measurement is explained in the Helios practical workshops, and
this is the easiest way to adjust a KWL EC 200/300 W R/L. In this respect, a pressure measuring
connector must be mounted to each connecting socket/ventilation pipe (approx. 20 cm past the unit
connection), and the pressure hoses must be readily accessible.
To balance the whole system, supply and extract openings should be provided with adjustable elements
or valves (accessories). During extraction of polluted extract air, a filter (accessories) is to be
connected. The installation of kitchen hoods to the system (cause: dirt, fire danger, hygiene) is not
permitted. To ensure air circulation within the room sufficient overflow openings (door gap, door grilles)
are to be planned.
ATTENTION
All fire regulations must be observed!
TIP!
Detailed information on the adjustment of KWL wall-mounted units can be found in the
Installation and Operating InstructionsKWL easyControls Initial start-up; No. 82 237!
When using a heating coil, the duct system must be provided with temperature-resistant and non-
flammable ducts (e.g. spiral duct) 1m before and after the heating coil.